TWINSPOT SPACING DATA (1 LUX AVERAGE)
Mounting
Spacing to
Between
Height
Wall
Units
2 x 21 Watt Tungsten Versions
2.5 metres
3m
9m
4 metres
4m
11m
6 metres
3m
12m
8 metres
3m
10m
2 x 20 Watt Halogen Versions
2.5 metres
5m
15m
4 metres
6m
16m
6 metres
5m
16m
8 metres
4m
15m
2 x 55 Watt Tungsten Halogen Versions
8 metres
15m
30m
10 metres
15m
30m

 

Notes: These tables are based on the following factors:

Light output ratios measured to BS5225 and lamp lumen outputs are from GE Lighting Warm white lamps.

Requirements from BS5266/EN1838

Permanently unobstructed escape routes:

Require minimum 0.2 lux along the centre line of the escape route, where there is a possibility of an obstruction occurring along the route 1 lux minimum is required.

Undefined, Open areas

The minimum level of illumination required throughout the are is 0.5 lux excluding a half metre border around the edge of the room which can be at a lower level.