TWINSPOT
SPACING DATA (1 LUX AVERAGE) |
Mounting |
Spacing
to |
Between |
Height |
Wall |
Units |
2
x 21 Watt Tungsten Versions |
||
2.5 metres |
3m |
9m |
4 metres |
4m |
11m |
6 metres |
3m |
12m |
8 metres |
3m |
10m |
2
x 20 Watt Halogen Versions |
||
2.5 metres |
5m |
15m |
4 metres |
6m |
16m |
6 metres |
5m |
16m |
8 metres |
4m |
15m |
2
x 55 Watt Tungsten Halogen Versions |
||
8 metres |
15m |
30m |
10 metres |
15m |
30m |
Notes: These tables are based on the following factors: Light output ratios measured to BS5225 and lamp lumen outputs are from GE Lighting Warm white lamps. Requirements from BS5266/EN1838 Permanently unobstructed escape routes: Require minimum 0.2 lux along the centre line of the escape route, where there is a possibility of an obstruction occurring along the route 1 lux minimum is required. Undefined, Open areas The minimum level of illumination required throughout the are is 0.5 lux excluding a half metre border around the edge of the room which can be at a lower level. |