Gives a Visual Indication of Zonal Fire Away from the Fire Panel

This repeater/indication panel gives remote indication of a zonal fire.

Easy to install, just two wires are required from the repeater to the fire output of the fire panel. It does not require an external power supply and can be surface mounted with the supplied back box or semi-flush with the use of a standard 25mm two gang back box.

 

Features
LED Indicators for general and zone fires
Operates on two wires from the fire output contacts on the panel
Up to three repeaters can be connected to the panel (dependant on other loads)
Can be mounted semi-flush via a standard two gang 25mm back box or surface mounted with the supplied back box
Zintec plated sheet steel construction with a textured polyester powder coated finish
Ordering Codes
FPR-001 Semi-Flush Repeater Indicator Panel
FPR-002 Surface Repeater Indicator Panel
Dimensions
Semi-Flush: 145mm x 85mm x 10mm
Surface: 145mm x 85mm x 25mm
Specification
Input Voltage: 18-30V dc
Input Current Consumption: 20mA ± 3mA
Max Repeaters Per Panel: 3 In Full Alarm #
No of Fire Zone LED's: 8 + 1 General Fire
Weight (Semi-Flush) 0.3Kg
Weight (Surface): 0.4Kg
 # Dependant on Other Loads