A Range of EN54 Compliant Conventional Fire Panels Incorporating a wide Range of Features |
![]() |
Our Range of conventional fire panels incorporate a wide range of features and are fully compliant with EN45 parts 2 and 4 and BS5839 part 1 for detector removal. The panels are compatible with a range of detectors making them especially suitable for retro-installation. Available in 2 zone, 4 zone and 8 zone variations, the fire panel continuously monitors all connections between detectors, manual call points and sounders and checks its own back-up batteries and power supply for faults. When a fault is detected, the panel provides both visual and audible indications. A unique mode indicator used in the panel’s on-board diagnostic system greatly simplifies programming, installation and general usage by indicating short or open circuits, healthy, disabled and time-delayed zones. Fire Panel semi-recessing bezels are available, please refer to our sales team for details.
|
Ordering Codes |
Fire
Panels |
Cat
No |
Zone
Circuits |
Sounder
Circuits |
Recommended
Batteries |
Dimensions |
Weight
* |
FP-002 |
2 |
2 |
24
Hrs 2x2.1Ah/72 Hrs 2x4Ah |
260mm
x 210mm x 82mm |
2.8Kg |
FP-004 |
4 |
2 |
24
Hrs 2x2.1Ah/72 Hrs 2x4Ah |
260mm
x 210mm x 82mm |
2.8Kg |
FP-008 |
8 |
4 |
24
Hrs 2x3.2Ah/72 Hrs 2x4Ah |
260mm
x 310mm x 82mm |
3.6Kg |
†
To be ordered separately * Excluding Batteries |
|||||
Options |
| Cat No | Description |
| FPA-198 | Semi-Recessing Bezel to suit FP-002 and FP-004 |
| FPA-199 | Semi-Recessing Bezel to suit FP-008 |
One
Man Test This allows an engineer to test field detections without
the need to return to the panel to reset it. Sounders will operate for
about 3 seconds before the panel automatically resets (Zone selectable) |
|
Class
Change Input This is a non-latching input that operates from
an external timer unit. It can be used to signal a change of lesson, start
and end of school/work and break times. |
|
End
of Line The end of line capacitor ensures compliance with BS5839
part 1 for detector removal and gives a very low running current. |
|
Fire/Fault
Relay This relay is commonly used to give a fault signal to external
equipment. The relay can be reconfigured so it operates on a fire signal
and will give an output to external equipment. |
|
Fire
Output (Monitored) Can be connected to heavy duty relays to operate
plant shutdowns, door holders, auto-diallers and fire dampers.
|
|
Auxiliary
28 Volt Output Can be used to supply external power to equipment
up to a maximum of 250mA. |
|
Zone
Reset This gives a 10 second +28 Volt output pulse to reset beam
detectors and other equipment. |
|
Disablement
Fire zones, alarm circuits, earth monitoring and fire outputs can all
be easily disabled by the user. |
|
Fault
Indication The panel can indicate an open circuit fault or a
short circuit fault on the mode indicator, O for open circuits and S for
short circuit *when accessed by the user controls). |
|
Coincidence
Detection (Double Knock) This is used to help eliminate false
alarms on control sprinkler systems and vital plant shutdowns (Two zones
need to be in fire before the fire outputs operate). |
|
Non-Latching
Zone This function can be used to interconnect two or more panels.
When a non-latching zone is in fire, the fire outputs do not operate,
thus making it ideal for use in a shop unit on a landlords system. |
|
Delayed
Zones This feature will give time for an event to be investigated
before the fire outputs operate. |
|
Time
Delay This feature will give delay on the zones (1-9 Minutes). |
|
Alarm
Modes You can select three alarm modes; Mode 1 is continuous
alarms, mode 2 is pulsed alarms and mode 3 is pulsed for one zone in fire
and continuous for two or more zones. |
|
Default
The panel can easily be returned to its factory default settings. |
|
Material
1.2mm Zintec plated sheet steel construction with a textured polyester
powder coated finish. |
| Features |
7
segment display mode indicator |
|
Class
change facility |
|
1.5
Amp power supply |
|
Key
access |
|
Supports
a wide range of detectors including System Sensor, Hochiki, Nittan and
Apollo |
|
Earth
terminals are provided on the terminal board to ease termination of the
earth drain wires |
|
Fully
compliant with BS5839 Part 1 and also EN54 Parts 2 and 4 |
|
One
man test facility |
| Typical System Schematic |

| Technical Information |
Power
Supply |
Sounder
Circuits |
||
Mains Supply Voltage: |
230V AC ± 10% 50/60Hz | End of Line Resistor Value: | 4K7 5% 0.25W |
| Internal Power Supply: | 28V DC Nominal | Open/Short Circuit Monitored: | Yes (Common Fault) |
| Total Output Current Limited To: | 1.5A | Alarm Sounder Circuit Voltage: | 28V DC Max 20V Min |
| Supply/Battery Charger Monitor: | Yes | Alarm Sounder Circuit Fuses: | 0.5A Resetable Fuse Each |
| Battery/Disconnection Monitor: | Yes | Max Total Sounder Load: | Up to 0.5A Each (1A Total) |
| Mains Fuse: | 230V 315mA(T) Anti-Surge | Max No of Bells (At 25mA): | 40 (Polarised & Suppressed) |
| Battery Fuse: | 2.5A Resetable Fuse | Max No of Sounders (At 20mA): | 50 (Polarised) |
Detector
Circuits |
Fire
Outputs |
||
| End of Line Capacitor Value: | 10uF 35V Electrolytic | No of Circuits: | 1 |
| Max Cable Length per Circuit: | 500M | End of Line Resistor Value: | 4K7 5% 0.25W |
| Open/Short Circuit Monitored: | Yes | Open/Short Circuit Monitored: | Yes (Fire Output Fault) |
| Detector Removal Monitored: | Yes | Fire Output Circuit Voltage: | 28V DC Max 20V Min |
| Maximum Line Resistance: | 22R | Fire Output Circuit Fuses: | 0.5A Resetable Fuse |
| Maximum Cable Capacitance: | 1uF | Max Total Fire Output Load: | Up to 0.5A Each (1A Total) |
| Call Point Resistor Value: | 470R-680R | Max No of Repeaters (At 100mA): | 3 (In Full Alarm #) |
| Max No of Detectors Per Zone: | 32 (No limit for Call Points) | Max Zonal Relays (At 160mA): | 2 (In Full Alarm #) |
General |
Auxiliary
Outputs |
||
| Cable Entry Knock-Outs | Top and Back | Common Fault Relay: | Volt Free SPDT 30V 1A |
| Operating Temperature: | +5°C to 35°C | Reset Output: | 28V 0.25A Resetable Fuse |
| Relative Humidity: | 5% to 95% Non-Condensing | Aux 28V Power Output: | 0.25A Resetable Fuse |
Semi-Recessing
Bezels |
Auxiliary
Inputs |
||
Construction: |
Powder
Coated Sheet Steel |
Class
Change: |
0V
Trigger Non-Latching |