Combining Seven modes of Detection and a Sounder all Within One Device

The multi-function detector is the key to all of our two-wire systems and offers seven different modes of detection and a sounder in one device.

The mode of detection required is changed simply by configuring the DIL switch in the detector's electronics module.

The multi-function detector can be supplied with or without an integral 90bDA sounder.

Compact and easy to install, the multi-function detector is fully compliant with all European detector type specifications and is suitable for installations compliant with BS5839 Part1 1988.

Features
Three smoke detection modes
Three heat detection modes (Two fixed, on rate of rise)
Combination standard heat or smoke mode
Can support up to 32 devices per zone Modes can be changed before and after installation
Available with or without an integral 90dBA sounder
Intelligent detector - Microprocessor controlled
Continuous self-calibration
Disposable optical chamber (No need for cleaning and can be economically replaced)
Two high-performance optical smoke and heat sensors (Optical scatter smoke sensor, temperature sensor)
Fully encapsulated electronics
Compact and easy to install
Ordering Codes
Cat No Description
FPA-1010 Combined Smoke/Heat Detector
FPA-1009 Combined Smoke/Heat Detector/90dB Sounder
FPA-1016 Detector/Sounder Head Removal Tool
FPA-1018 Multi-function Device Replacement Chamber
Technical Information

Operating Voltage:

15 to 28 Volts dc (20 Volts dc Nominal)
Detector Operating Current: Quiescent 60µA, Alarm 39mA
Sounder Operating Current: Quiescent Nil, Alarm 39mA
Sounder Alarm Levels: Normal Setting 90dBA, Low Setting 75dBA
Dimensions: Ø 105mm x 32mm Height
Weight: 270g
Modes of Detection
Smoke 1 Used where ionisation detectors are normally fitted, especially when the application has high ceilings or is susceptible to the risk of free burning fires.
Smoke 2 Used where optical detectors are normally fitted when there is a risk of a smoldering fire and for escape routes.
Smoke 3 Used where optical detectors are normally used in positions exposed to brief concentrations of water vapour or smoke e.g. from a bathroom, kettle etc.
Heat 1 Used where a standard rate of rise detector would normally be used.
Heat 2 Used where a standard 58°C fixed temperature detector would normally be fitted e.g. commercial kitchens.
Heat 3 Used where a standard 90°C fixed temperature detector would normally be fitted e.g. boiler rooms.
Smoke 2/Heat 2 A Combination of smoke 2 and heat 2 will trigger from either a smoke or heat source.