| Multi-Protocol Networkable Analogue Addressable Fire Alarm Controls Panels |
![]() |
Adept analogue addressable fire panels have been designed and constructed around proven and reliable microprocessor technology. This provides a modular, scalable fire alarm platform suitable for protecting a vast range of premises such as offices, hospitals and industrial units. The Adept panel supports five industry-leading protocols, namely System Sensor, Morley-IAS, Apollo, Hochiki and Nittan, which allows fire detection devices to be selected based on performance and aesthetic preference. The required loop card must be ordered separately. Designed for maximum adaptability, the Adept panel allows information on the location of fires, faults and system status to be easily accessed and displayed or printed at multiple locations. The flexibility and intelligence of the Adept analogue addressable panel ensure it's suitability for many installations such as new projects, retrofit and system expansion upgrades. |
| Features | |
Integrates
with System Sensor, Morley-IAS, Apollo (Xplorer, XP95 and Discovery),
Hochiki ESP and Nittan detection device protocols |
|
Modular
concept |
|
Simple
and robust design |
|
Integration
to voice evacuation, paging and third party control systems is supported
through a range of peripheral interface units |
|
Easy
to install, configure, expand and maintain |
|
Ordering Codes |
| Fire Panels | ||||
| Cat No | Loops | Description | Weight* | Batteries |
| FP-030 | 1 |
400mm x 400mm x 135mm | 9.3Kg | 2 x 12Ah |
| FP-031 | 2 |
400mm x 400mm x 135mm | 10.0Kg | 2 x 12Ah |
| FP-032 | 5 |
500mm x 500mm x 195mm | 19.0Kg | 2 x 24Ah |
| * Excluding Batteries (to be ordered separately) | ||||
| Ancillaries | |
| Cat No | Description |
| FPA-191 | System Sensor Loop Driver Card |
| FPA-148 | Morley-IAS Loop Driver Card |
| FPA-188 | Apollo XP95 & Discovery Loop Driver Card |
| FPA-189 | Apollo S90 Loop Driver Card |
| FPA-192 | Nittan Loop Driver Card |
| FPA-190 | Hochiki ESP Loop Driver Card |
| FPA-149 | RS232 Communication Card (2 & 5 Loop Panels Only) |
| FPA-150 | RS485 Communication Card |
| FPA-151 | 20 Zone LED Display Indicator Card (2 & 5 Loop Panels) |
| FPA-152 | 60 Zone LED Display Indicator Card (2 & 5 Loop Panels) |
| FPA-153 | Internal Printer (5 Loop Panel Only) |
| FPA-157 | 4 Way Programmable Relay Module, PCB Only |
| FPA-158 | 4 Way Programmable Sounder Module, PCB Only |
| FPA-159 | 8 Way Programmable Input Module, PCB Only |
| FPA-160 | 40 Way Programmable Mimic Interface Module, PCB Only |
| FPA-161 | Hi-485 Communication Module, PCB Only (2 & 5 Loop Panels) |
| FPA-162 | Adept / Adroit Active Repeater (Key Activated) |
| FPA-163 | Adept / Adroit Passive Repeater |
| FPA-164 | 1 & 2 Loop Panel Bezel Kit |
| FPA-165 | 5 Loop Panel Bezel Kit |
| FPA-166 | Adept Repeater Bezel Kit |
| FPA-167 | External Remote Printer Module |
| FPA-168 | MODBUS Interface Unit |
| FPA-169 | Paging System Interface Module |
| Typical System Schematic |

The System The Adept control panel is the heart of the fire detection system and contains all of the required components, microprocessor, power supply with a clear liquid crystal display, system status indicator and the control buttons, which as the user interface. System users can easily assess the condition of the fire alarm system as alarm and fault conditions are highlighted by LED's and are supported by enhanced text descriptions on the LCD display. Clearly labeled buttons allow the user to quickly manipulate the system as required The use of user pass codes to gain access to functions ensures that malicious or accidental operation is prevented. Basic functions (Evacuate, Reset, Mute, Accept, Silence) are available at the first access level, whilst more advanced operations such as single device isolations, test modes and configuration data are protected by secondary level pass codes. Microprocessor's within each control panel maintain a log of events or actions occurring on the system. Fires, fault, tested devices and diagnostics are all electronically logged for future reference. The Adept control panel can be configured to support any one of the five detection protocols (System Sensor, Morley-IAS, Apollo, Hochiki and Nittan) by simply installing the correct loop driver cards in the controls panel. Installation Initial installation of the system is greatly aided by Autolearn, which is an internal routine that automatically detects all devices on the detection and peripheral loops, therefore saving time on entering all devices individually. Basic programming is also configured during the Autolearn, process, resulting in only fine tuning of the system being required to complete the system configuration. Maintenance The Adept control panels has been designed to provide standard weekly testing through s simple menu structure, allowing a selection of zones to be tested and also for the optional activation of the outputs and sounders. Individual devices can be analysed to determine whether cleaning or complete replacement is required. The information can either be viewed on the LCD or printed to produce a 'hard' copy. Networking Up to 99 controls panels can be networked together using the standard control panel operating system. The network can be configured in two ways; For single sites or large buildings, the networking is usually configured as a large system with each networked control panel sharing information. For multiple sites or buildings, the networking usually operates in a report and control mode. The panels act individually or as sub-system reporting information to the master panel on the level above. |
| Specification | |
| Zones: | Up
to 20 zones with individual LED indicators (5 Loop versions expandable
to 40 or 80). A maximum 200 can be programmed with up to 180 software
zones with no LED indication (5 Loop versions 120). |
| Internal Sounder: | Intermittent
buzzer (Fault condition). High-pitched continuous buzzer (Fire condition) |
| External Outputs: | |
- Sounder Outputs: |
2
(or 4 on 5 loop versions) programmable outputs. Open and short circuit
monitoring. 1A maximum per output. |
| - Auxiliary Relays | EN54
format at 1 fault relay and 1 programmable relay voltage free, changeover
outputs contacts rated at 24V ac/dc, 1A, 0.6pF maximum. |
| User Controls: | MUTE,
ACCEPT, SILENCE/RESOUND, SOUND ALARMS & RESET |
| Programming Controls: | Alphanumeric
multi-level keypad with 15 keys and 3 control keys: |
| General Panel LED Indicators: | FIRE,
FAULT, ACCEPTED, DISABLEMENT, TEST, SOUNDER, FAULT, DELAYED MODE, REPLAYS
DISABLED, EARTH FAULT, SYSTEM.CPU FAULT, SOUNDERS DISABLED, ALARMS SILENCED,
SUPPLY FAULT, POWER. |
| Zone LED Indicators: | FIRE,
FAULT/TEST/DISABLED (For 20 Zones). |
| Display: | 2
x 40 character LCD alphanumeric display with back-light. |
| Networking: | Maximum
99 panels can be networked using a master network and connected sub-networks. |
| Technical Information |
| Details | FPA-030
(1 Loop) |
FPA-031
(2 Loop) |
FPA-032
(5 Loop) |
| Operating Voltage: | 230V
50Hz ac (± 10% Voltage Tolerance) |
230V
50Hz ac (± 10% Voltage Tolerance) |
230V
50Hz ac (± 10% Voltage Tolerance) |
| Max PSU Rating: | 2.5
Amps |
2.5
Amps |
3.25
Amps |
| Minimum Battery Capacity: | 2
x 12V 6Ah Sealed Lead Acid |
2
x 12V 6Ah Sealed Lead Acid |
2
x 12V 12Ah Sealed Lead Acid |
| Maximum Battery Capacity: | 2
x 12V 12Ah Sealed Lead Acid |
2
x 12V 12Ah Sealed Lead Acid |
2
x 12V 12Ah Sealed Lead Acid |
| Power Supply Inputs: | 24V
and 7Vac |
24V
and 7Vac |
24V
and 7Vac |
| Power Supply Outputs: | 24Vdc
Nominal (26.5-19.5Vdc) |
24Vdc
Nominal (26.5-19.5Vdc) |
24Vdc
Nominal (25.5-20.0Vdc) |
| Operating Temperature: | 0°C
to +40°C |
0°C
to +40°C |
0°C
to +40°C |
| Humidity: | 85%
Non-Condensing Maximum |
85%
Non-Condensing Maximum |
85%
Non-Condensing Maximum |
| Construction: | Powder-Coated
Sheet Steel, IP30 Rated |
Powder-Coated
Sheet Steel, IP30 Rated |
Powder-Coated
Sheet Steel, IP30 Rated |
| Cable Entry: | 14
x 20mm Knock-Outs (Cabinet Top) |
14
x 20mm Knock-Outs (Cabinet Top) |
34
x 20mm Knock-Outs (Cabinet Top) |
| Loop Capacity: | 1
Loop |
1 to 2 Loops Expandable |
1
to 5 Loops Expandable |
| Apollo/Nittan/Hochiki Protocols: | Max
126 Devices Per Loop |
Max
126 Devices Per Loop |
Max
126 Devices Per Loop |
| Morley/System Sensor Protocols: | Max 99 Sensor Addresses Per Loop |
Max
99 Sensor Addresses Per Loop |
Max
99 Sensor Addresses Per Loop |
Max
99 Module Addresses Per Loop |
Max
99 Module Addresses Per Loop |
Max
99 Module Addresses Per Loop |
|
| Serial Interface: | 1
x Serial Port with RS485 Connections |
2
x Serial Port with RS485 and RS232 Connections |
3
x Serial Port with RS485 and RS232 Connections |