| A Range of LPCB Approved Devices to Support the ADEPT & ADROIT Addressable Fire Panels |
![]() |
The Adept and Adroit range of addressable devices are fully approved by the Loss Prevention Certification Board and offer maximum benefits to the installer and end-user. Addressable sensors feature an aesthetically pleasing low profile design and a built-in functional test activated by an external magnet. All heat sensors have two integral alarm LED's, giving a local visual indication of the sensor's status. Loop powered and base sounders lend a co-ordinate series of high performance, high quality products to the Adept and Adroit range. The efficiency and low current consumption of the sounders allow a greater number of sounders to be powered from a single loop. The range of sounders have been designed with ease of installation in mind and feature large terminals for both incoming and outgoing cables. |
Adept and Adroit addressable call points are fitted with a built in monitoring module, which provides an interface to the detection loop. Call points are addressed by dialling in the address using the rotary switches on the rear of the unit. An IP67 waterproof call point is available for external applications. Addressable output modules are used for operating external equipment such as door holders, air handling unit shut down or other similar functions. Alternatively, the output modules can be used to monitor the external load voltage. If the monitored voltage falls below it's threshold, then a fault condition will be indicated. |
Ordering Codes |
| Sensors | Sounders | ||
| Cat No | Description | Cat No | Description |
| FPA-170 | Optical
Smoke Sensor |
FPA-178 | Loop Powered Base Sounder |
| FPA-171 | Ionisation
Smoke Sensor |
FPA-179 | Loop Powered Wall Sounder (Red) |
| FPA-172 | High
Sensitivity Laser Smoke Sensor |
FPA-180 | Loop Powered Wall Sounder (White) |
| FPA-173 | Combined
Smoke/Heat Sensor |
FPA-211 | Red Wall Mounted Loop Powdered High Output Sounder |
| FPA-174 | 57°C
Fixed Heat Sensor |
FPA-212 | White Wall Mounted Loop Powdered High Output Sounder |
| FPA-175 | 78°C
Fixed Heat Sensor |
FPA-207 | Red Deep Base Back Box to Suit FPA-179 |
| FPA-176 | Rate
of Rise Heat Sensor |
FPA-208 | White Deep Base Back Box to Suit FPA-180 |
| FPA-177 | Sensor
Base |
FPA-209 | Red Sealed Base Back Box to Suit FPA-179 |
| FPA-221 | Sensor
Mounting Base Fitted With Built-In Isolator |
FPA-210 | White Sealed Base Back Box to Suit FPA-180 |
| Modules | FPA-181 | Base Sounder Blanking Cap (Red) | |
| FPA-186 | Output
Module |
FPA-182 | Base Sounder Blanking Cap (White) |
| FPA-187 | Control
Output Module |
Strobe | |
| FPA-213 | Micro
Monitor Module with Status LED Output |
FPA-222 | Red Wall Mounted Loop Powered Strobe |
| FPA-214 | Conventional
Zone Monitor Module |
Call points | |
| FPA-215 | Single
Input Monitor Module |
FPA-183 | Red Call Point (Without Back Box and Glass) |
| FPA-216 | Dual
Input & Single Output Combination Module |
FPA-184 | Call Point Back Box |
| FPA-220 | Surface
Loop Isolator Module |
FPA-185 | IP67 Weatherproof Call Point |
| FPA-218 | Surface
Mounting Box to Suit FPA-214 |
FPA-036 | Replacement Glasses (Pack of 5) |
| FPA-219 | Surface
Mounting Box to Suit FPA-215 |
| Specification |
| Smoke & Heat Sensors | |
| Operating Voltage: | 15-32Vdc |
| Current Consumption: | |
| - Stand By Current | 200µA at 24Vdc |
| - LED Current | 7mA at 24Vdc ("On") |
| Operating Temp Range: | -10°C to +60°C |
| Relative Humidity: | 10% to 93% Non-Condensing |
| Sounders/Strobe | |
| Operating Voltage: | 15-30Vdc |
| Current Consumption: | |
| -High Volume | 7.3mA |
| -Standard Volume | 4.1mA |
| Output Volume Level: | |
| -High Volume | 100dBA ± 3db at 1m |
| (90dBA Base) | |
| -Standard Volume | 93dBA ±3dB at 1m |
| (85dBA Base) | |
| Flash Rate (Strobe): | 0.5Hz |
| Operating Temp Range: | -10°C to +60°C |
| Relative Humidity: | 10% to 93% Non Condensing |
| Laser Smoke Detectors | |
| Operating Voltage: | 15-32Vdc |
| Stand By Current: | |
| -No Communication | 230µA at 24Vdc |
| -LED Blink | 330µA at 24Vdc |
| Operating Temp Range: | -10°C to +55°C |
| Relative Humidity: | 10% to 93% Non-Condensing |
| Alarm Current: | 7mA at 24Vdc Maximum |
| Call Points | |
| Operating Voltage: | 15-32Vdc |
| Current Consumption: | |
| Stand By Current: | 200µA at 24Vdc |
| -LED Current | 7mA at 24Vdc |
| Operating Temp Range: | -10°C to +60°C |
| Relative Humidity: | 10% to 93% Non-Condensing |
| Combined Smoke/Heat Detectors | |
| Operating Voltage: | 15-32Vdc |
| Stand By Current: | |
| -No Communication | 250µA at 24Vdc |
| -LED Blink | 300µA at 24Vdc |
| Operating Temp Range: | -20°C to +60°C |
| Alarm Current: | 7mA 24Vdc Maximum |
| Modules | |
| Output Rating: | 5A Resistive Load |
| (30Vdc & 24Vdc) | |
| Operating Temp: | -20°C to +60°C |
| Relative Humidity: | 0% to 95% Non-Condensing |